What IS a BoilerMate 2000?
(Firstly, most Boilermates are qualified with II, III or 2000 or
similar suffixes. The first, original BoilerMate was just called a
BoilerMate without suffix. This page deals with the BoilerMate 2000)
How does the BoilerMate 2000 work?
A conventional central heating boiler heats the water in the
BoilerMate 2000 directly. The stored water is pumped to the boiler for
heating and back again by the left-hand of the three pumps behind the
front panel of the unit
whenever the stored water temperature drops below a specific temperature
set in the factory. The centre pump pumps water around the radiator
circuits when central heating is required.
The BoilerMate 2000 delivers hot water to the hot taps in a similar
way to the previous BoilerMate III, but without the user-adjustable
thermostatic blender valve. The right-hand pump starts when a hot tap is
turned on and pumps hot store water through the plate heat exchanger,
thus heating the cold mains water very effectively on it's way to the
hot taps or showers.
The two separate circuit boards behind the cover panel on the
BoilerMate III are now replaced by a single combined control board
controlling every function. The appliance Control Board (ACB). There are
no user-controllable parameters.
Faults known to occur in the BoilerMate 2000:
1) Depleted water in the thermal store.
BoilerMate 2000s have a filling cistern fitted above them, which
is there to fill the unit with water. This
may or may not have a float valve connected to the mains water supply to
fill it. When there is NO mains connection, there is usually provision
for manual filling by the user by means of a tap on the wall nearby.
When the user doesn't realise this, water lost from the thermal store through
evaporation and/or leaks can prevent the unit from working. If the water
level falls too low, eventually there s too little water for the pumps
to pump, the unit will make gurgling noises and stop delivering hot water. The answer is to check the
water level in the top-up cistern and top it up.
2) Circulating pump failure
BoilerMate 2000s sometimes fail to deliver ANY hot water to the taps
at all. After a random amount of time the hot taps start working again.
This is usually a sticking hot water circulating pump. The quick fix is
to fit a new one, but the underlying cause is usually system corrosion
caused by absence of corrosion inhibitor in the initial fill of system
water. A powerflush is necessary to prevent the problem
re-occurring.
3) Water scale-contamination of the plate heat exchanger.
The plate heat exchanger was hailed by manufacturers as the answer to
water scaling, but this has proved not to be the case. Hard water in
certain areas still seems capable of blocking a plate heat exchanger
with calcium deposits causing restricted hot water flow from the taps
and warm (instead of hot) temperatures. When the problem becomes acute
the water flow slows to a trickle and the temperature swings wildly from
scalding hot to stone cold. The answer is to fit a
replacement plate heat exchanger, which takes around an hour (instead of
several hours to de-scale the copper coil heat exchanger in early
versions of the BoilerMate)..
4) Heat sensor failure.
Hot water temperature from the taps and/or shower becomes unreliable
and unpredictable. The hot water temperature sensor delivers a signal to
the ACB board and this controls the pump speed. They seem to fail with
age (after three or four years) and replacement restores reliable hot
water performance. I believe they are thermistors but there is more to
them than that as there are three conductors in the leads. Their true
nature is shrouded in secrecy. No-one at Gledhill gives anything away
when I ask questions... quite frustrating really but I'll get to the
bottom of them eventually....!
5) Continuous operation of central heating.
The central heating runs continuously, refusing to respond to the
room thermostat being turned down or the timer being turned OFF. It's
control board failure. A new control board fixes the problem.
If you'd like me to come and fix your BoilerMate 2000, contact
me now!
|